KEW 6024PV

Availability:

In stock


• Correct measuring for Insulation resistance even if the panel is under generating power
• Waterproof design: Can measure under the bad weather condition
• Memory function up to 1000 data
• Luminescence button and Backlight

Product Catalogue

LKR 386,600

In stock

Get 15% discount on Sampath Cards with installments plans.
Compare

KEW 6024PV

Size
Colour
Type
Insulation resistance PV insulation Insulation
Test voltage 500V 1000V 250V 500V 1000V
Measuring range
(Auto range)
20.00/200.0/2000MΩ 20.00/200.0/2000MΩ
Mid-scale value 50MΩ
Rated current 1.0-1.2mA
0.25MΩ 0.5MΩ 1MΩ
First effective
measuring range
1.51-200.0MΩ 1.51-1000MΩ 1.51-100.0MΩ 1.51-200.0MΩ 1.51-1000MΩ
Accuracy ±1.5%rdg±5dgt ±1.5%rdg±5dgt
Second effective
measuring range
0.00-1.50MΩ 0.00-1.50MΩ 1.20-1.50MΩ 1.20-1.50MΩ 1.20-1.50MΩ
200.1-2000MΩ 1001-2000MΩ 100.1
-2000MΩ
200.1
-2000MΩ
1001
-2000MΩ
Accuracy ±5.0%rdg±6dgt
Open circuit voltage 0 – +20%
Short circuit current Max 1.5mA
Earth resistance
Measuring range
(Auto range)
20.00/200.0/2000Ω
Accuracy ±3.0%rdg±0.1Ω (20Ωrange) ±3.0%rdg±3dgt (200/2000Ωrange)
Voltage measurement
Measuring range AC 5-600V (45-65Hz)DC ±5-±1000V
Accuracy ±1.0%rdg±4dgt
General
Applicable Standards IEC 61010-1 CAT Ⅲ 600V, CAT IV 300V Pollution2
IEC 61010-2-030, IEC 61010-031(EMC), IEC 60529(IP54),
IEC 61557-1,-2,-5,-10, IEC 61326-1,2-2, EN50581(RoHS)
Power source LR6(AA)(1.5V) x 6
Dimensions /
Weight
84(L) x 184(W) x 133(D)mm / Approx. 900g (including batteries)
Accessories 7196B(Test leads with remote control switch),
7244A(Test lead with alligater clip), 8017(Extension prod),
8072(CAT II standard prod),
8212-USB(USB adaptor with “KEW Report (Software)”),
9155(Shoulder strap), 9156A(Carrying case), LR6x6, Instruction manual
Optional 7243A(L-shaped probe), 7245A(Precision measurement cord set),
8016(Hook type prod)

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “KEW 6024PV”

There are no reviews yet.