KEW 6024PV INSULATION EARTH TESTER

Out of Stock

KEW 6024PV INSULATION EARTH TESTER

Accurate measuring of Insulation resistance even if the PhotoVoltaic (PV) arrays are generating power

  • Accurate measuring of Insulation resistance even if the PhotoVoltaic (PV) arrays are generating power
  • No need to short circuit the PV arrays or test at night to measure the Insulation resistance
  • Earth resistance measurements with Voltamperometric method at 3 and 2 pole
  • Waterproof design, ideally suited to work in bad weather condition
  • Memory function up to 1000 data
  • Luminescence buttons and large Backlight display
  • Elapsed time, after starting a measurement, is displayed with the measured values
  • Compact and light weight
  • Test probe with a remote control switch is supplied as standard accessory
  • Auto-discharge with voltage display
  • Special analysis software “KEW Report” is available

Product Catalogue

LKR 396,510

Out of stock

Easy Payment Plans

Sampath Bank Payment Plans
The installment payment calculations now include the VAT(18%) amount of Rs.71371.8, bringing the total cost to Rs.467881.8. All displayed amounts reflect this inclusive pricing for complete transparency.
Month(s) Handling Fee (%) Monthly (Approx) Total (Approx)
3 0.00% 155,960.60 467,881.80
6 0.00% 77,980.30 467,881.80
Commercial Bank Payment Plans
The installment payment calculations now include the VAT(18%) amount of Rs.71371.8, bringing the total cost to Rs.467881.8. All displayed amounts reflect this inclusive pricing for complete transparency.
Month(s) Handling Fee (%) Monthly (Approx) Total (Approx)
6 0.00% 77,980.30 467,881.80

Specification

PV Insulation resistance*
Test voltage 500V 1000V
Range(Auto-ranging) 20.00/200.0/2000MΩ
Measuring range 0.00 to 1.50MΩ
200.1 to 2000MΩ
1.51 to 200.0MΩ 0.00 to 1.50MΩ
1001 to 2000MΩ
1.51 to 1000MΩ
Accuracy ±5%rdg±6dgt ±1.5%rdg±5dgt ±5%rdg±6dgt ±1.5%rdg±5dgt
Open circuit voltage 1 to 1.2times
Short circuit current 1.5mA or less
Insulation resistance
Test voltage 250V 500V 1000V
Range(Auto-ranging) 20.00/200.0/2000MΩ
Rated current 1.0 to 1.2mA
0.25MΩ 0.5MΩ 1MΩ
First effective measuring range 1.51 to 100.0MΩ 1.51 to 200.0MΩ 1.51 to 1000MΩ
Mid-scale value 50MΩ
Accuracy ±1.5%rdg±5dgt
Second effective measuring range 1.20 to 1.50MΩ
100.1 to 2000MΩ
1.20 to 1.50MΩ
200.1 to 2000MΩ
1.20 to 1.50MΩ
1001 to 2000MΩ
Accuracy ±5.0%rdg±6dgt
Open circuit voltage 1 to 1.2times
Short circuit current 1.5mA or less
Earth resistance
Measuring range(Auto-ranging) 20.00/200.0/2000Ω
Accuracy ±3.0%rdg±0.1Ω (20Ω range)
±3.0%rdg±3dgt (200/2000Ω range)
Voltage measurement
Measuring range AC 5 to 600V (45 to 65Hz) DC ±5 to 1000V
Accuracy ±1.0%rdg±4dgt
General
Applicable Standards IEC 61010-1 CAT Ⅳ 300V / CAT Ⅲ 600V Pollution degree 2
IEC 61010-2-030, IEC 61010-2-034, IEC 61010-031, IEC 60529(IP54)
IEC 61557-1,2,5,10, IEC 61326-1,2-2
Power source LR6(AA)(1.5V) × 6
Dimension 84(L) × 184(W) × 133(D)mm
Weight Approx. 900g (including batteries)
Accessories 7196B(Test leads with remote control switch)
7244A(Test lead with alligator clip)
8017(Extension prod long)
8072(CATⅡStandard prod)
8212-USB(USB adapter)
9156A(Soft case with shoulder strap)
LR6(AA) × 6,
Instruction manual
Optional Accessories 7243A(L-shaped probe)
7245A(Precision measurement cord set)
8016(Hook type prod)

Please download “KEW Report(software)” from here.

*6024PV supports PV systems up to 1000V.

Reviews

There are no reviews yet.

Be the first to review “KEW 6024PV INSULATION EARTH TESTER”

Your email address will not be published. Required fields are marked *

Related Products

In Stock

KEW 1020R DIGITAL MULTIMETER
LKR 41,750

Out of stock

SimpliFiber® Pro Optical Pow...

Out of stock

FI-500 FiberInspector™ Micro...

Out of stock

Fiber Optic Cleaning Kits

Out of stock

OptiFiber® Pro OTDR Family

Out of stock

Fiber QuickMap™

Out of stock

FI-7000 FiberInspector™ Pro

Out of stock

Fluke Networks Pro3000™ Tone...

Out of stock

Fluke Networks LinkIQ™ Cable...

Out of stock

Fluke Networks Industrial Et...

Product Search

Request Quote