DISPLAY                     Color LCD 3.5 inches dot matrix.
ATT                               Anti-Trip Technology (with 2 & 3 wire) for no trip LOOP L-PE testing on all RCDs.
                                       ・With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines).
LOOP                           ・High test current range of 2Ω with 0.001Ω resolution.
・Zs Limit compares the values required by Electrical Installations Standard with measured results.
RCD                              ・Type AC, A, F, B(General & Selective), EV and Variable RCDs.
・Single and Auto test, Ramp test and Contact voltage.
EARTH                       ・Earth resistance test 2 and 3 wires with all accessories included.
INSULATION           ・Resistance test 100, 250, 500 & 1000V with auto discharge voltage.
CONTINUITY           ・Continuity test at 200mA or 15mA with selectable buzzer for fast judgment.
PHASE ROTATION・On 3-phase lines with clear indication of the sequence on the display.
VOLTS                         ・TRMS Voltage measurements 2-600V, Mains Frequency.
HELP                           ・Display shows how to connect the instrument according to the function selected.
SPD                              ・Surge Protection Device test, for SPD that uses varistor.
PAT                              ・Portable Appliance Tester function, for Insulation and Protective conductor resistance test
SAFETY                      ・IEC 61010-1 CAT IV 300 V, CAT III 600 V. IEC 61557-1,2,3,4,5,6,7,10.

Large LCD & HELP function
  • All the test data is shown in one large colored screen.
  • HELP function will show how to connect the instrument according to the function selected

Operation in 3 simple steps & Hands free testing
  1. Set the rotary dial to your testing range.
  2. Connect the instrument to the installation under test.
  3. Press the test button.(By remote probe or using the Lockdown function of the test button.)

 

Anti-Trip Technology (with 2 & 3 wire)

For no trip LOOP L-PE testing on all RCDs.
With 3 wire (L, N, PE), to get the best accuracy readings.
With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines).

Loop Impedance 0.001 resolution

High test current range of 2Ω with 0.001Ω resolution.

Zs/Ra Limit

Zs Limit compares the values required by Electrical Installations Standard with measured results.

The verification of safety requirement on an electrical installation is simplified by using Zs/Ra Limit function. This function will automatically check if the measured loop impedance for TN (or earth loop for TT) is low enough to trip (disconnect) the MCB / Fuse / RCD giving the result of PASS or FAIL on the display.

SPD test

SPD (Surge Protection Device) which contains varistor can be tested measuring the tripping voltage without damage it.

PAT test

PAT test (PAT = Portable Appliance Tester) It is possible to check the insulation resistance and earth bond continuity of portable appliances for class I and II.

Connectivity

Use the PC application KEW Report to improve work efficiency.

KEW 6516 can download the test data by connecting the USB adaptor (Model 8212-USB) and then print complete Test Reports by a PC.

 

KEW 6516

Size
Colour
Type

Various features

Insulation resistance SPD(Varistor)
Test
voltage
100V 250V 500V 1000V Max.1000V
Measuring
ranges
2.000/20.00/200.0MΩ
(Auto-ranging)
20.00/200.0/1000MΩ
(Auto-ranging)
20.00/200.0/2000MΩ
(Auto-ranging)
0-1000V
(goes up by 1V)
Accuracy ±2%rdg±6dgt
(2.000/20.00MΩ)
±5%rdg±6dgt
(200.0MΩ)
±2%rdg±6dgt
(20.00/200.0MΩ)
±5%rdg±6dgt
(1000MΩ)
±2%rdg±6dgt
(20.00/200.0MΩ)
±5%rdg±6dgt
(2000MΩ)
±5%rdg±5dgt
Rated
current
1.0-1.2mA
@0.1MΩ
1.0-1.2mA
@0.25MΩ
1.0-1.2mA
@0.5MΩ
1.0-1.2mA
@1MΩ
Short circuit current 1.5mA max
Loop impedance
Function LOOP ATT LOOP HIGH
L-PE/L-N
(3wire)
L-PE
(2wire)
L-PE
(0.01ΩRes)
L-PE
(0.001ΩRes)
High test
current(25A)
L-N/L-L
Rated
voltage
100-260V
(50/60Hz)
48-260V
(50/60Hz)
48-260V
(50/60Hz)
100-260V
(50/60Hz)
48-500V
(50/60Hz)
Impedance
range
20.00/200.0/2000Ω
(Auto-ranging)
20.00/200.0/
2000Ω
(Auto-ranging)
2.000Ω 20.00Ω
Accuracy ±3%rdg±6dgt ±3%rdg±10dgt ±3%rdg±4dgt ±3%rdg±25mΩ ±3%rdg±4dgt
Nominal
test
current at
0Ω external
loop:
Magnitude/
Duration at 230V
L-N:6A/60ms
N-PE:10mA
L-PE:15mA 20Ω:
6A/20ms
200Ω:
0.5A/20ms
2000Ω:
15mA/500ms
25A/20ms 6A/20ms
PSC/PFC
Range 2000A/20kA
(L-N(PSC)/
L-PE(PFC))
2000A/20kA
(PFC)
2000A/20kA
(PFC)
2000A/50kA
(PFC)
2000A/20kA
(PSC)
Accuracy PSC/PFC accuracy is derived from measured loop impedance specification
and measured voltage specification
RCD
Rated voltage 100-260V(50/60Hz)
Function x1/2, x1,x5,Ramp,Auto,Uc
6/10/30/100/300/500/1000mA/variable
RCD type AC(G/S) A(G/S) F(G/S) B(G/S) EV
Trip
current
setting
x1/2,
x1,Uc
10/30/100/300/
500/1000mA(G)
10/30/100/
300/500(S)
10/30/100/
300/500mA
10/30/100/
300/500mA
10/30/100/
300mA
6mA(x1 only)
x5 10/30/100mA 10/30/100mA 10/30/100mA 10/30mA
Ramp 10/30/100/
300/500mA
10/30/100/
300/500mA
10/30/100/
300/500mA
10/30/100/
300mA
6mA
Accuracy
Trip
current
x1/2 -8% – -2% -10% – 0% -10% – 0% -10% – 0%
x1 +2% – +8% 0% – +10% 0% – +10% 0% – +10% 0% – +10%
x5 +2% – +8% 0% – +10% 0% – +10% 0% – +10%
Ramp -4% – +4% -10% – +10% -10% – +10% -10% – +10% -10% – +10%
Trip
time
x1/2 2000ms(G/S):±1%rdg±2ms
x1 550ms(G):±1%rdg±2ms,1000ms(S):±1%rdg±2ms 10.5s:±1%±2㎳
x5 410ms(G/S):±1%rdg±2ms
Continuity
Range 20.00/200.0/2000Ω (Auto-ranging)
Open circuit voltage(DC) 7-14V
Measuring current 200mA >200mA or more(2Ω or less)
15mA 15mA±3mA(short-circuit)
Accuracy ±2%rdg±8dgt
Volts
Range 300.0/600V(Auto-ranging)
Measuring ranges Volts 2-600V
Frequency 45-65Hz
Accuracy Volts ±2%rdg±4dgt
Frequency ±0.5%rdg±2dgt
Phase Rotation
Rated voltage 48-600V(50/60Hz)
Remarks Remarks Correct phase sequence: are displayed “1.2.3” and mark
Reversed phase sequence: are displayed “3.2.1” and mark
Earth
Range 20.00/200.0/2000Ω(Auto-ranging)
Accuracy ±2%rdg±0.08Ω(20.00Ω)
±2%rdg±3dgt(200.0/2000Ω)
Applicable standards IEC 61010-1 CAT IV 300V ,CAT III 600 V Pollution degree 2
IEC 61010-2-034
IEC 61557-1,2,3,4,5,6,7,10
IEC 60529(IP40)
IEC 61326(EMC)
Power source LR6 (AA) (1.5V) ×8
Communication interface USB
Dimensions / Weight 136(L) × 235(W) × 114(D) mm / Approx. 1350g (including batteries)
Included Accessories Main test lead※1
7281(Test leads with remote control switch)
7246(Distribution board test lead)
7228A(Earth resistance test leads)
8041(Auxiliary earth spikes[2 spikes/1 set])
9084(Soft case)
9142(Carrying case)
9151(Shoulder strap)
9199(Shoulder pad)
8212-USB(USB adaptor with “KEW Report(Software)”)
LR6(AA) × 8, Instruction manual, Calibration certificate
Optional Accessories 8259(Adapter for measurement terminal)
7272(Precision measurement Cord set)
8017A(Extension prod long)

※1 7187A:British plug, 7218A:(EU)European SHUKO plug, 7221A:(SA)South african plug, 7222A:(AU)Australian plug

Based on 0 reviews